This example integrates pandapower and GridLAB-D™ to perform an integrated
transmission (bulk power system) and distribution powerflow.

Includes functionality to support microstepping to achieve better convergence
of the physical state of the system as modeled in each tool. Iteration at the 
same time step is not supported by GridLAB-D™ so instead we microstep through 
time (1 second steps). Pandapower is stateless so for just solving powerflow
so no need to do anything fancy there, just rerun the powerflow with the 
updated load from GridLAB-D™ at each microstep. Users can set the number of 
microsteps to take at each main time step with the `microstep_max` parameter.
Minimum value of `microstep_max` is 1, which means the simulation will just 
step forward in increments of the main time step size (i.e. no microstepping).

Also included are two plotting methods, one using matplotlib and one using 
plotly. Pick the one you want by setting the "plotting_tool" parameter to 
either "matplotlib" or "plotly". The plotly option will save an interactive
HTML file that can be opened in a web browser.


@author: Trevor Hardy
trevor.hardy@pnnl.gov
"""

import gridlabd
from pathlib import Path
import os
from pprint import pprint
from datetime import datetime, timedelta
import pandapower as pp
import pandapower.networks as pn
import math



def plot_coupled_signals(sim_time_points, voltage_magnitude, load_magnitude):
    """Plot coupled T&D values with dual y-axes over simulated time."""
    try:
        import matplotlib.pyplot as plt
    except ImportError as err:
        raise ImportError(
            "matplotlib is required for plot_coupled_signals. Install with 'pip install matplotlib'."
        ) from err

    fig, ax_voltage = plt.subplots(figsize=(11, 5))
    ax_load = ax_voltage.twinx()

    ax_voltage.plot(
        sim_time_points,
        voltage_magnitude,
        color="tab:blue",
        linewidth=2,
        label="|Pandapower Voltage Applied to GridLAB-D|",
    )
    ax_load.plot(
        sim_time_points,
        load_magnitude,
        color="tab:red",
        linewidth=2,
        label="|GridLAB-D™ Load Applied to Pandapower|",
    )

    ax_voltage.set_xlabel("Simulated Time")
    ax_voltage.set_ylabel("Voltage Magnitude (V)", color="tab:blue")
    ax_load.set_ylabel("Load Magnitude (MVA)", color="tab:red")
    ax_voltage.tick_params(axis="y", labelcolor="tab:blue")
    ax_load.tick_params(axis="y", labelcolor="tab:red")
    ax_voltage.grid(True, alpha=0.3)

    lines_left, labels_left = ax_voltage.get_legend_handles_labels()
    lines_right, labels_right = ax_load.get_legend_handles_labels()
    ax_voltage.legend(lines_left + lines_right, labels_left + labels_right, loc="best")

    fig.tight_layout()
    plt.show()


def plot_coupled_signals_plotly(
    sim_time_points,
    voltage_magnitude,
    load_magnitude,
):
    """Plot coupled T&D values with Plotly and save an interactive HTML file."""
    try:
        import plotly.graph_objects as go
        from plotly.subplots import make_subplots
    except ImportError as err:
        raise ImportError(
            "Plotly is required for plot_coupled_signals_plotly. Install with 'pip install plotly'."
        ) from err

    fig = make_subplots(specs=[[{"secondary_y": True}]])

    fig.add_trace(
        go.Scatter(
            x=sim_time_points,
            y=voltage_magnitude,
            mode="lines",
            name="|Pandapower Voltage Applied to GridLAB-D|",
            line={"color": "royalblue", "width": 3},
        ),
        secondary_y=False,
    )

    fig.add_trace(
        go.Scatter(
            x=sim_time_points,
            y=load_magnitude,
            mode="lines",
            name="|GridLAB-D™ Load Applied to Pandapower|",
            line={"color": "firebrick", "width": 3},
        ),
        secondary_y=True,
    )

    fig.update_xaxes(title_text="Simulated Time")
    fig.update_yaxes(title_text="Voltage Magnitude (V)", secondary_y=False)
    fig.update_yaxes(title_text="Load Magnitude (MVA)", secondary_y=True)
    fig.update_layout(
        title="Coupled Transmission/Distribution Signals",
        template="plotly_white",
        hovermode="x unified",
        legend={"x": 0.01, "y": 0.99},
    )


    return fig

# User-defined parameters
step_size = 300
microstep_max = 3
plotting_tool = "matplotlib"  # Options: "matplotlib" or "plotly"


# Ensure's we're running from the correct directory
script_path = os.path.abspath(__file__)
script_dir = os.path.dirname(script_path)
os.chdir(script_dir)

# Since pandapower isn't going to move through times (and just run the same
# powerflow at each time step, only getting a slightly updated load from
# GridLAB-D™ each time), only the load on the GridLAB-D™ side should
# appreciably change.
starttime = datetime(2026, 7, 1, 0, 0, 0)
stoptime = datetime(2026, 7, 2, 0, 0, 0)
pp_bus_coupling_index = 40
voltage_scaling_factor = 1.0
load_scaling_factor = 1.0


# Setting up GridLAB-D
gld = gridlabd.GridLabD()
model_path = Path("house_with_solar")
response_working = gld.set_working_directory(str(model_path))
if response_working != 0:
    raise RuntimeError(
        f"Failed to change working directory to {model_path} with response code: {response_working}"
    )
response_load = gld.load("houses.glm")
if response_load != 0:
    raise RuntimeError(
        f"Failed to load model in {model_path} with response code: {response_load}"
    )
gld.set_starttime(starttime.isoformat())
gld.set_stoptime(stoptime.isoformat())
gld.set_time_step(step_size)

# Setting up pandapower
net118 = pn.case118()
coupling_load_rows = net118.load.index[net118.load["bus"] == pp_bus_coupling_index]
if coupling_load_rows.empty:
    raise ValueError(
        f"No pandapower load rows found at bus index {pp_bus_coupling_index}"
    )
coupling_load_row = coupling_load_rows[0]

# Setting up integrated T&D powerflow
sim_duration = stoptime - starttime
num_steps = int(sim_duration.total_seconds() / step_size)

# Calculating scaling factor after running each tool for one step
pp.run.runpp(net118)
gld.step()
gen_at_bus = net118.gen[net118.gen.bus == pp_bus_coupling_index]


# Diagnostics to confirm the bus we're coupling GridLAB-D™ to will have a
# varying voltage. Generally not needed during normal runs.
# Checking to see if a generator is at the bus we're attaching the
# GridLAB-D™ load to.
# if gen_at_bus.empty:
#     print(f"No pandapower generator found at bus index {pp_bus_coupling_index}.")
# pv_buses = net118.gen.bus.unique()
# print(f"PV buses: {pv_buses}")
# slack_buses = net118.ext_grid.bus.unique()
# print(f"Slack buses: {slack_buses}")

# Voltage from pandapower will be applied to GridLAB-D™, thus the scaling
# factor is calculated as the ratio of GridLAB-D™ voltage to pandapower
# voltage
gld_voltage_str = gld.get_object_property_value(
    "network_node", "positive_sequence_voltage"
)
gld_voltage = complex(gld_voltage_str.replace("i", "j"))
pp_voltage = net118.bus.at[pp_bus_coupling_index, "vn_kv"] * 1000 * math.sqrt(3)
voltage_scaling_factor = abs(gld_voltage) / abs(pp_voltage)
pp_base_voltage = net118.bus.at[pp_bus_coupling_index, "vn_kv"] * 1000 * math.sqrt(3)
# Load from GridLAB-D™ will be applied to pandapower, thus the scaling
# factor is calculated as the ratio of pandapower load to GridLAB-D™ load
gld_load = gld.get_object_property_value("network_node", "distribution_load")
pp_load = (
    complex(
        net118.load.at[coupling_load_row, "p_mw"],
        net118.load.at[coupling_load_row, "q_mvar"],
    )
    / 1000000
)
load_scaling_factor = abs(pp_load) / abs(gld_load)

# Store magnitudes for post-simulation visualization.
sim_time_points = []
applied_voltage_magnitude = []
applied_load_magnitude = []

# Run the integrated T&D powerflow simulation, stepping through simulation
# time
microstep_count = 0
gld.set_time_step(1)
for step in range(num_steps - 1):
    status, sim_time = gld.get_time()    
    sim_time_obj = datetime.fromisoformat(sim_time)
    while microstep_count < microstep_max:
        status, current_time = gld.get_time()
        current_time_obj = datetime.fromisoformat(current_time)
        pp.run.runpp(net118, calculate_voltage_angles=True)
        pp_voltage_pu = net118.res_bus.at[pp_bus_coupling_index, "vm_pu"]
        gld_substation_voltage = float(
            abs(pp_voltage_pu * pp_base_voltage * voltage_scaling_factor)
        )
        gld.set_property(
            "network_node", "positive_sequence_voltage", gld_substation_voltage
        )
        
        time_code, sim_time_str = gld.step()
        if time_code != 0:
            raise RuntimeError(f"Simulation step failed at {sim_time_str} with error code {time_code}.")
        sim_time_dt = datetime.fromisoformat(sim_time_str)

        # Check for errors
        messages = gld.get_messages()
        filtered_messages = [
            message for message in messages
            if message.get("type") in {"ERROR"}
        ]
        if filtered_messages:
            pprint(filtered_messages)
        gld.clear_messages()
        
        complex_load = gld.get_object_property_value("network_node", "distribution_load")
        t_load = complex_load * 1000000 * load_scaling_factor
        net118.load.at[coupling_load_row, "p_mw"] = t_load.real
        net118.load.at[coupling_load_row, "q_mvar"] = t_load.imag
        microstep_count += 1

    # Storing data for post-processing visualization
    sim_time_points.append(sim_time_obj)
    applied_voltage_magnitude.append(abs(gld_substation_voltage))
    applied_load_magnitude.append(abs(t_load))

    # Move to next large time-step size
    gld.step_to(datetime.isoformat(sim_time_obj + timedelta(seconds=step_size)))
    microstep_count = 0

gld.stop()
gld.exit_gld()
print("Simulation complete. Now plotting results...")

if plotting_tool == "matplotlib":
    plot_coupled_signals(sim_time_points, applied_voltage_magnitude, applied_load_magnitude)
elif plotting_tool == "plotly":
    plot_coupled_signals_plotly(
        sim_time_points, applied_voltage_magnitude, applied_load_magnitude
    ).show(renderer="browser")
else:
    raise ValueError(f"Invalid plotting tool specified: {plotting_tool}")
 