Load Tracker
Warning
The load_tracker class is deprecated and will be removed in a future release.
The load_tracker object monitors a property on some "target" object (e.g., real power, magnitude of complex power, etc.) and adjusts an output scaling value so that the measured load tracks a user-defined setpoint. Other objects in the model can then read this output value to scale their behavior.
Sample
object load_tracker
{
name RECLOSER_1_LOAD_TRACKER;
target RECLOSER_1;
target_property power_in;
operation MAGNITUDE;
setpoint 145000;
deadband 1.0; // Ensure double_assert.within > 219000 * deadband (as a percent)
damping 0.0;
full_scale 219000; // Note: This is the sum of the base powers
// from the 2 downstream loads. It does
// not take account of line losses but
// is the expected value users would enter
}
object load
{
name LOAD_2;
parent NODE_4;
phases ABC;
nominal_voltage 6350.85;
base_power_A RECLOSER_1_LOAD_TRACKER.output*22000;
base_power_B RECLOSER_1_LOAD_TRACKER.output*22000;
base_power_C RECLOSER_1_LOAD_TRACKER.output*22000;
power_fraction_A 0.5;
power_fraction_B 0.5;
power_fraction_C 0.5;
current_fraction_A 0.25;
current_fraction_B 0.25;
current_fraction_C 0.25;
impedance_fraction_A 0.25;
impedance_fraction_B 0.25;
impedance_fraction_C 0.25;
power_pf_A 0.9;
power_pf_B 0.9;
power_pf_C 0.9;
current_pf_A 0.8;
current_pf_B 0.8;
current_pf_C 0.8;
impedance_pf_A 0.8;
impedance_pf_B 0.8;
impedance_pf_C 0.8;
};
Load Tracker Parameters
Properties
load_tracker does not declare inherited parent classes.
The I/O column indicates whether a property is user-settable input (I), simulation-computed output (O), or both (IO).
| Property Name | Type | Unit | I/O | Description |
|---|---|---|---|---|
| target | object | N/A | I | target object to track the load of |
| target_property | char256 | N/A | I | property on the target object representing the load |
| operation | enumeration | N/A | I | operation to perform on complex property types Valid values: REAL, IMAGINARY, MAGNITUDE, ANGLE. |
| full_scale | double | N/A | I | magnitude of the load at full load, used for feed-forward control |
| setpoint | double | N/A | I | load setpoint to track to |
| deadband | double | N/A | I | percentage deadband |
| damping | double | N/A | I | load setpoint to track to |
| output | double | N/A | IO | output scaling value |
| feedback | double | N/A | O | the feedback signal, for reference purposes |