Power Metrics
The power_metrics object is used by the reliability module to calculate relevant powerflow metrics. The power_metrics object calculates the IEEE 1366-2003 metrics for evaluating the reliability indices of a power system.
For detailed information about reliability analysis and the metrics computed by this object, see the Reliability User Guide.
A minimalist power_metrics implementation is
object power_metrics {
name PwrMetrics;
}
with an equivalent of
object power_metrics {
name PwrMetrics;
base_time_value 60.0;
}
power_metrics objects are primarily output objects.
Power Metrics Parameters
Properties
power_metrics does not declare inherited parent classes.
The I/O column indicates whether a property is user-settable input (I), simulation-computed output (O), or both (IO).
| Property Name | Type | Unit | I/O | Description |
|---|---|---|---|---|
| SAIFI | double | N/A | IO | The simulation-long computed value of the System Average Interruption Frequency Index |
| SAIFI_int | double | N/A | IO | The interval-long computed value of the System Average Interruption Frequency Index. The interval is defined by the base_time_Value property. |
| SAIDI | double | N/A | IO | The simulation-long computed value of the System Average Interruption Duration Index |
| SAIDI_int | double | N/A | IO | The interval-long computed value of the System Average Interruption Duration Index. The interval is defined by the base_time_Value property. |
| CAIDI | double | N/A | IO | The simulation-long computed value of the Customer Average Interruption Duration Index. |
| CAIDI_int | double | N/A | IO | The interval-long computed value of the Customer Average Interruption Duration Index. The interval is defined by the base_time_Value property. |
| ASAI | double | N/A | IO | The simulation-long computed value of the Average Service Availability Index. |
| ASAI_int | double | N/A | IO | The interval-long computed value of the Average Service Availability Index. The interval is defined by the base_time_Value property. |
| MAIFI | double | N/A | IO | The simulation-long computed value of the Momentary Average Interruption Frequency Index |
| MAIFI_int | double | N/A | IO | Displays MAIFI values over the period specified by base_time_value as per IEEE 1366-2003 |
| base_time_value | double | s | I | Interval duration for IEEE 1366-2003 statistics to be computed. This information is the basis for any time calculations. For example, the interruption duration for a CAIDI calculation can be interruptions per hour, interruptions per minute, or any other time base. base_time_value dictates this base for the calculations. The value defaults to 1 minute. |
Power Metrics State of Development
The power_metrics object is tested and validated with the reliability module. However, it has not been fully validated and is considered experimental at this time.