Triplex Load
Triplex load is similar to load and ZIPload in that load can be specified as a direct value, or as a base load, then a ZIP fraction applied to that base load. The load can be placed on phase 1 (120V), phase 2 (120V) or phase 12 (240V). Much like the load object, player objects can be used to vary the load with time. triplex_load objects provide a means to implement constant current, constant power, and constant impedance losses or generation into the system. The convention is a load is a positive quantity, so generation would need to be represented as a negative number.
Example Triplex Load
Loads can be a mixture of the constant current, constant impedance, and constant power types. A typical, mixed load would be implemented as
object triplex_load {
phases "AS";
name tplex_load;
constant_current_1 -0.586139+9.765222j;
constant_impedance_2 221.915014+104.430595j;
constant_power_12 4200.00+2100.00j;
nominal_voltage 120.0;
}
Triplex Load Parameters
triplex_load objects are derived from triplex_node objects, so any parameters of the triplex_node object are available as well.
The I/O column indicates whether a property is user-settable input (I), simulation-computed output (O), or both (IO).
General Properties
| Property Name | Type | Unit | I/O | Description |
|---|---|---|---|---|
| load_class | enumeration | N/A | I | Describes the type of load the object represents. Used for informational purposes only. Valid types may be referenced by keyword or number 0 - U - Unknown load type 1 - R - Residential load 2 - C - Commercial load 3 - I - Industrial load 4 - A - Agricultural load |
| load_priority | enumeration | N/A | I | Load classification based on priority. Valid values: DISCRETIONARY, PRIORITY, CRITICAL. |
ZIP Load Properties
These properties define constant power, constant current, and constant impedance loads directly. The _1, _2, and _12 variants represent loads on phase 1 (to neutral), phase 2 (to neutral), and phase 12 (between phases/delta) respectively. The _real and _reac suffixed variants provide access to the real and imaginary components individually.
| Property Name | Type | Unit | I/O | Description |
|---|---|---|---|---|
| constant_power_1 | complex | VA | IO | Constant power load on phase 1 (to neutral). |
| constant_power_2 | complex | VA | IO | Constant power load on phase 2 (to neutral). |
| constant_power_12 | complex | VA | IO | Constant power load on phase 12 (between phases, delta connection). |
| constant_power_1_real | double | W | IO | Constant power load on phase 1, real only. |
| constant_power_2_real | double | W | IO | Constant power load on phase 2, real only. |
| constant_power_12_real | double | W | IO | Constant power load on phase 12, real only. |
| constant_power_1_reac | double | VAr | IO | Constant power load on phase 1, imaginary only. |
| constant_power_2_reac | double | VAr | IO | Constant power load on phase 2, imaginary only. |
| constant_power_12_reac | double | VAr | IO | Constant power load on phase 12, imaginary only. |
| constant_current_1 | complex | A | IO | Constant current load on phase 1 (to neutral). |
| constant_current_2 | complex | A | IO | Constant current load on phase 2 (to neutral). |
| constant_current_12 | complex | A | IO | Constant current load on phase 12 (between phases, delta connection). |
| constant_current_1_real | double | A | IO | Constant current load on phase 1, real only. |
| constant_current_2_real | double | A | IO | Constant current load on phase 2, real only. |
| constant_current_12_real | double | A | IO | Constant current load on phase 12, real only. |
| constant_current_1_reac | double | A | IO | Constant current load on phase 1, imaginary only. |
| constant_current_2_reac | double | A | IO | Constant current load on phase 2, imaginary only. |
| constant_current_12_reac | double | A | IO | Constant current load on phase 12, imaginary only. |
| constant_impedance_1 | complex | Ohm | IO | Constant impedance load on phase 1 (to neutral). |
| constant_impedance_2 | complex | Ohm | IO | Constant impedance load on phase 2 (to neutral). |
| constant_impedance_12 | complex | Ohm | IO | Constant impedance load on phase 12 (between phases, delta connection). |
| constant_impedance_1_real | double | Ohm | IO | Constant impedance load on phase 1, real only. |
| constant_impedance_2_real | double | Ohm | IO | Constant impedance load on phase 2, real only. |
| constant_impedance_12_real | double | Ohm | IO | Constant impedance load on phase 12, real only. |
| constant_impedance_1_reac | double | Ohm | IO | Constant impedance load on phase 1, imaginary only. |
| constant_impedance_2_reac | double | Ohm | IO | Constant impedance load on phase 2, imaginary only. |
| constant_impedance_12_reac | double | Ohm | IO | Constant impedance load on phase 12, imaginary only. |
Measurement Properties
These properties are computed by the simulation and are output only. Note that the measured_voltage properties lag by one powerflow iteration; for the most current values, read the corresponding voltage_* properties from the parent triplex_node object directly.
| Property Name | Type | Unit | I/O | Description |
|---|---|---|---|---|
| measured_voltage_1 | complex | V | O | Measured voltage on phase 1. |
| measured_voltage_2 | complex | V | O | Measured voltage on phase 2. |
| measured_voltage_12 | complex | V | O | Measured voltage on phase 12 (between phases). |
| indiv_measured_power_1 | complex | VA | O | Measured power on phase 1. |
| indiv_measured_power_2 | complex | VA | O | Measured power on phase 2. |
| indiv_measured_power_12 | complex | VA | O | Measured power on phase 12. |
| measured_power | complex | VA | O | Total measured power. |
Base Power and ZIP Fraction Properties
These properties provide an alternative way to specify ZIP loads using a base power value with fraction and power factor breakdowns per phase, following the same conventions as the ZIPload object. When base_power is nonzero for a phase, it overrides the corresponding constant_power, constant_current, and constant_impedance values for that phase.
| Property Name | Type | Unit | I/O | Description |
|---|---|---|---|---|
| base_power_1 | double | VA | I | Nominal power on phase 1 before applying ZIP fractions. |
| base_power_2 | double | VA | I | Nominal power on phase 2 before applying ZIP fractions. |
| base_power_12 | double | VA | I | Nominal power on phase 12 before applying ZIP fractions. |
| power_pf_1 | double | pu | I | Power factor of the phase 1 constant power portion of load. |
| current_pf_1 | double | pu | I | Power factor of the phase 1 constant current portion of load. |
| impedance_pf_1 | double | pu | I | Power factor of the phase 1 constant impedance portion of load. |
| power_pf_2 | double | pu | I | Power factor of the phase 2 constant power portion of load. |
| current_pf_2 | double | pu | I | Power factor of the phase 2 constant current portion of load. |
| impedance_pf_2 | double | pu | I | Power factor of the phase 2 constant impedance portion of load. |
| power_pf_12 | double | pu | I | Power factor of the phase 12 constant power portion of load. |
| current_pf_12 | double | pu | I | Power factor of the phase 12 constant current portion of load. |
| impedance_pf_12 | double | pu | I | Power factor of the phase 12 constant impedance portion of load. |
| power_fraction_1 | double | pu | IO | Constant power fraction of base power on phase 1. May be overwritten if ZIP fractions do not sum to 1. |
| current_fraction_1 | double | pu | I | Constant current fraction of base power on phase 1. |
| impedance_fraction_1 | double | pu | I | Constant impedance fraction of base power on phase 1. |
| power_fraction_2 | double | pu | IO | Constant power fraction of base power on phase 2. May be overwritten if ZIP fractions do not sum to 1. |
| current_fraction_2 | double | pu | I | Constant current fraction of base power on phase 2. |
| impedance_fraction_2 | double | pu | I | Constant impedance fraction of base power on phase 2. |
| power_fraction_12 | double | pu | IO | Constant power fraction of base power on phase 12. May be overwritten if ZIP fractions do not sum to 1. |
| current_fraction_12 | double | pu | I | Constant current fraction of base power on phase 12. |
| impedance_fraction_12 | double | pu | I | Constant impedance fraction of base power on phase 12. |
Triplex Load State of Development
Triplex_load is considered a well developed and validated model, with a number of features. Additional features may be included as needed.